CIF-Module CANopen | Wilo
Similar to figure

CIF-Module CANopen

Technical data
Tender text

Interface module as retrofittable plug-in module for extending the communication interfaces of the pump in accordance with various standards and protocol variants according to type key.

General functions

Serial, digital interface for connection to building automation for the transfer of data points as:

  • Control commands to the pump
  • Messages from the pump
  • Process values

Equipment

CAN 2.0A interface with CANopen protocol

Information about the download

http://www.wilo.de/automation (German)

http://www.wilo.com/automation (English)

Scope of delivery

  • CIF module
  • 2x threaded cable glands M16x1.5 (suitable for Stratos MAXO)
  • Installation and operating instructions

Bus lines (shielded!) must be provided by the customer

Technical data
Line type
CAN bus cable, twisted in pairs, shielded, 1 x 2 x 0.5 mm² / 120 Ω characteristic impedance (line type B in accordance with TIA 485-A)
Line length
200 m
Spur line
max. 10 m, max. total 50 m
Terminal cross-section
1,5 mm²
Interface
CAN in accordance with ISO 11898-2, optically insulated
Speed
125 kBit/s, constant
Format
-
Protocol
CANopen in accordance with CiA DS301 V 4.02
Profile
-
Net weight, approx.
0.06 kg
Make
Wilo
Item no.
2190369
Downloads

Certificate REACH (Documents)

REACH regulation

Edition 2020-08
Page format 209.9 x 297.0 mm
Number of pages 2