More flexibility with integrated interfaces
Whether retrofitted or installed directly in the pump - Wilo products offer you various interfaces so that they can be optimally integrated into the building automation system.
Water Supply
High-pressure multistage centrifugal pumps
Pressure-boosting systems
Integrated
Potential-free contracts:
- SSM
- SBM
Digital interfaces
- extern AUX
- AUX
Analogue interfaces
- 0-20 mA
- 4-20 mA
Twin-head function
- available
Bus interfaces:
- Modbus RTU
Optional
Bus interfaces:
- Modbus RTU/TCP
- BACnet MS/TP
- LON TP/FT-10
- Modbus TCP
- BACnet/IP
Product example
- Wilo-SiBoost Smart Helix EXCEL
Building Services
Smart pumps
Integrated
Potential-free contracts
- SSM
- SBM
Digital interfaces
- Wilo-Stratos MAXO: 2 inputs, freely configurable
- Wilo Stratos GIGA 2.0: 4 inputs, freely configurable
Analouge interfaces
- 2 inputs
- 0-10 V
- 2-10 V
- 0-20 mA
- 4-20 mA
- PT 1000
Twin-head function
- available
Optional
Bus interfaces:
- Modbus RTU/TCP
- BACnet MS/TP
- LON TP/FT-10
- CANopen
- PLR
- Ethernet multiprotocol
Product example
- Wilo-Stratos MAXO
- Wilo-Stratos GIGA 2.0
Glanded pumps
Integrated
Potential-free contracts:
- SSM
- SBM
Digital interfaces
- 2 inputs, freely configurable
Analouge interfaces
- 2 inputs
- 0-10 V
- 2-10 V
- 0-20 mA
- 4-20 mA
- DDG
Twin-head function
- available
Optional
Bus interfaces:
- Modbus RTU/TCP
- BACnet MS/TP
- LON TP/FT-10
- CANopen
- PLR
- Ethernet multiprotocol
Product examples
Systems
Integrated
Potential-free contracts:
- SSM
- SBM
Digital interfaces
- extern AUX
- AUX
Analouge interfaces
- 2 inputs
- 0-10 V
- 2-10 V
- 0-20 mA
- 4-20 mA
Twin-head function
- available
Optional
Bus interfaces:
- Modbus RTU
- BACnet MS/TP
- LON TP/FT-10
- Modbus TCP
- BACnet/IP
- Modbus TCP
- BACnet /IP
Product example
- Wilo-SiFlux 3 IL-E
Example with the Wilo-Stratos MAXO:
Our Wilo-Stratos MAXO smart pump offers you analog and digital interface located directly in the terminal compartment of the pump. For connection to the building automation via a bus protocol, the retrofittable CIF module is used.
ANALOGUE INTERFACES
- 0 – 10 V, 2 – 10 V, 0 – 20 mA, 4 – 20 mA for the remote setpoint adjustment
- PT1000 temperature sensor for the feed and/or return temperature
DIGITAL INTERFACES
Operational information and control commands can be transmitted to the building automation system via digital interfaces. Many Wilo products have digital inputs with which control modes can be triggered and duty points can be requested:
- External OFF
- External MAX
- External MIN
- External key lock
- External MANUAL
- Heating/cooling switchover
POTENTIAL-FREE CONTACT FOR SSM AND SBM
Fault or run signals are transmitted via potential-free contacts such as collective fault signal (SSM) or collective run signal (SBM):
- SSM for fault feedback
- SBM for pump operation feedback