CronoBloc-BL 50/305-7,5/4
Article number: 9140217
Number of results: 1
Product design type | Glanded monobloc pump | Existing pump |
Description | ||
Product description | Atmos GIGA-B 50/305-7,5/4 | CronoBloc-BL 50/305-7,5/4 |
Article number | 9140217 | 9140217 |
Series | Wilo-Atmos GIGA-B | - |
Mains connection | - | 3~400 V ±10%, 50 Hz |
Pump connection | - | DN 65 |
Comment | Change piping | - |
Motor data | ||
Materials | ||
Pipe connection | ||
Dimension, weight | ||
Ordering information |
Hydraulic data | |
---|---|
Minimum efficiency index (MEI) | ≥0.4 |
Min. fluid temperature Tmin | -20 °C |
Max. fluid temperature Tmax | 140 °C |
Max. ambient temperature Tmax | 40 °C |
Maximum operating pressure PN | 16 bar |
Note on dimensioning | 16 bar to 120 °C, 13 bar to 140 °C |
Motor data | |
---|---|
Mains connection | 3~400 V, 50 Hz |
Number of poles | 4 |
Voltage tolerance | ±10 % |
Motor efficiency class | IE3 |
Rated power P2 | 7.5 kW |
Rated current IN | 16 A |
Rated speed n | 1450 1/min |
Power factor cos φ100 | 0.81 |
Motor efficiency 50% ηM 50% | 87.4 % |
Motor efficiency 75% ηM 75% | 89.3 % |
Motor efficiency 100% ηM 100% | 89.8 % |
Motor winding up to 3 kW | - |
Motor winding from 4 kW | - |
Insulation class | F |
Protection class motor | IP55 |
Motor protection | PTC integrated |
Materials | |
---|---|
Pump housing | 5.1301/EN-GJL-250 KTL-coated |
Impeller | Grey cast iron EN-GJL-200 |
Shaft | Stainless steel |
Mechanical seal | AQ1EGG |
Installation dimensions | |
---|---|
Pipe connection on the suction side DNs | DN 65 |
Pipe connection on the discharge side DNd | DN 50 |
CronoBloc-BL 50/305-7,5/4
∆: Connection diagram delta connection
Y: Connection diagram star connection
Motor protection switch required on-site. Check the direction of rotation! To change the direction of rotation, exchange any two phases.
P2≤ 3 kW | 3~400 V Y |
3~230 V ∆ | |
P2≥ 4 kW | 3~690 V Y |
3~400 V ∆ |
After removing the bridges, Y-∆ start is possible.