Stratos MAXO 32/0,5-16 PN6/10-R7-OEM
Glandless pump circulator
Data sheet
| Hydraulic data | |
|---|---|
| Maximum operating pressure PN | 10 bar |
| Head max H max | 16.2 m |
| Flow max Q max | 21.0 m³/h |
| Minimum suction head at 50 °C m | 5 m |
| Minimum suction head at 95 °C m | 12 m |
| Minimum suction head at 110 °C | 18 m |
| Min. fluid temperature Tmin | -10 °C |
| Max. fluid temperature Tmax | 90 °C |
| Min. ambient temperature Tmin | -10 °C |
| Max. ambient temperature Tmax | 40 °C |
| Motor data | |
|---|---|
| Energy efficiency index (EEI) * | ≤ 0.17 |
| Mains connection | 1~230 V ±10%, 50/60 Hz |
| Min current Imin | 0.2 A |
| Max current Imax | 2.23 A |
| Rated power P2 | 433 W |
| Min. speed nmin | 650 1/min |
| Max. speed nmax | 4950 1/min |
| Power consumption P1 min | 10 W |
| Power consumption P1 max | 510 W |
| Emitted interference | EN 61800-3;2004+A1;2012 /residential area (C1) |
| Interference resistance | EN 61800-3;2004+A1;2012 /industrial environment (C2) |
| Insulation class | F |
| Protection class | IPX4D |
| Threaded cable connection | 5 x M16x1.5 |
| Installation dimensions | |
|---|---|
| Pump connection | DN 32 |
| Port-to-port length L0 | 220 mm |
| Materials | |
|---|---|
| Pump housing | Grey cast iron |
| Impeller | PPS-GF40 |
| Shaft | 1.4028, DLC-coated |
| Bearing | Carbon-graphite |
Equipment/function
| Function | |
|---|---|
| Control mode | Δp-v for variable differential pressure Δp-c for constant differential pressure Q limit for limiting the maximum volume flow Dynamic Adapt plus ΔT-const. for constant differential temperature control T-const. for constant temperature control Constant Q for constant volume flow control Multi Flow Adaptation Δ T-const. for constant differential temperature control User-defined PID control Constant speed (n-const.) |
| Special features of the series | Heating/Cooling switching Night set back Heat quantity measurement Cooling quantity measurement Key locking function No-Flow Stop Reset function to factory setting Adjustable volume flow limiter Ability to save and restore configured pump settings (3 restoration points) Fault message and warning message in plain text including suggested remedy |
| Multi pump operation | Main/Standby Parallel operation |
| Measurement value logging | Heat and cooling capacity measurement |
| Display | Setpoint Actual delivery head Actual volume flow Actual power consumption Energy consumption Temperature (version “-R7”: current fluid temperature possible with Stratos MAXO temperature sensor) Warning messages in plain text (display status: yellow) Error messages in plain text (display: red) Pump venting (display status: blue) Control mode Active influences (e.g. STOP) |
| Display (can also be selected) | Speed Heating quantity Cooling quantity Operating hours Mains voltage Warning message Error message |
| Pump venting function | Yes |
| Equipment | |
|---|---|
| Approvals and labels | CE VDE EAC |
| Cold water insulation shell | As accessories |
| Display | Graphic colour display (4.3 inches) |
| Display information | Comfort Version: LCD display (large) for showing the head, flow volume, actual und cumulated current. |
| Pump control | Electronic-controlled pump |
| Quick electrical connection | Wilo Connector |
| Thermal insulation shell | Yes |
| Blocking-current proof motor | yes |
| Particle filter | yes |
| Key lock | yes |
| Connectivity | |
|---|---|
| Access via the Wilo-Assistant app | Yes |
| Analogue signal as standard | 0-10 V 2-10 V 4-20 mA 0-20 mA PT1000 |
| Bus communication via additional accessories | BACnet MS/TP LON Modbus RTU CANopen PLR BACnet IP Modbus TCP |
| Connection for Wilo-Smart Cloud | Via Wilo-Smart Gateway |
| Digital input | Ext. MAX Ext. MIN Ext. OFF Key lock MANUAL (BMS-OFF) Switchover between heating/cooling mode |
| Digital output | SSM SBM |
| wire data exchange and remote operation | Bluetooth |
Pump curves
Dimensions and dimensions drawings
Stratos MAXO 32/0,5-16 PN6/10-R7-OEM

Wiring diagram
Standard: 1~ 230 V, 50/60 Hz, Option: 3~ 230 V, 50/60 Hz

SSM: Collective fault signal (NC contact in accordance with VDI 3814, load capacity 1 A, 250 V ~)
Ordering information
| Product data | |
|---|---|
| Brand | Wilo |
| Product description | Stratos MAXO 32/0,5-16 PN6/10-R7-OEM |
| Article number | 2222146 |
| EAN number | 4062679242057 |
| Colour | Green/black/silver |
| Minimum order quantity | 1 |
| Date of sales availability | 2022-03-01 |
| Packaging | |
|---|---|
| Packaging type | Cardboard box |
| Packaging property | Transport packaging |
| Pieces per pallet | 8 |
| Number per layer | 4 |
| Dimension, weight | |
|---|---|
| Length with packaging | 600 mm |
| Length L | 400 mm |
| Height with packaging | 394 mm |
| Height H | 220 mm |
| Width with packaging | 400 mm |
| Width W | 243 mm |
| Gross weight, approx. m | 18.8 kg |
| Net weight, approx. m | 15.4 kg |
Wilo-Stratos MAXO-R7 premium smart-pump
High-efficiency pump as glandless pump with EC motor and electronic power adjustment. Can be used for heating water, chilled water and water/glycol mixtures. Energy efficiency index (EEI) between ≤ 0.17 and ≤ 0.19 depending on pump type.
Control modes:
- Permanent, automatic power adjustment to system requirements without setpoint specification Wilo Dynamic Adapt plus (factory setting).
- Constant temperature (T-const.)
- Constant differential temperature (dT-const.)
- Needs-based volume flow optimisation of the feeder pump through connectivity and communication between multiple pumps (Multi-Flow Adaptation).
- Constant volume flow (Q-const.)
- Differential pressure control (dp-c) at a remote point in the pipe network (index circuit evaluator)
- Constant differential pressure (dp-c)
- Variable differential pressure (dp-v) with the option to set the nominal duty point
- Constant speed (n-const.)
- User-defined PID control
Functions:
- Heat quantity measurement (possible with the optional Wilo fluid temperature sensor)
- Cooling quantity measurement (possible with the optional Wilo fluid temperature sensor)
- Pump switches off automatically when zero flow is detected (No-Flow Stop)
- Switchover between heating and cooling modes (automatic, external or manual) (automatic, possible with the optional Wilo fluid temperature sensor)
- Adjustable volume flow limiter using the Q-Limit function (Qmin. and Qmax.)
- Dual-pump operating modes: Efficiency-optimised parallel operation for dp-c and dp-v, main/standby mode
- Ability to save and restore configured pump settings (3 restoration points)
- Fault and warning messages displayed in plain text with advice on resolving the issue
- Pump venting function for automatic venting of the rotor chamber
- Automatic night setback (possible with the optional Wilo fluid temperature sensor)
- Automatic deblocking function and integrated full motor protection
- Dry-running detection
Display:
- Control mode
- Setpoint
- Volume flow
- Temperature (available with accessory Wilo fluid temperature sensor)
- Power consumption
- Electrical energy consumption
- Active influences (e.g. STOP, No-Flow Stop)
Version:
- 2 configurable analogue inputs: 0-10 V, 2-10 V, 0-20 mA, 4-20 mA and commercially available Pt1000; +24 V DC power supply
- 2 configurable digital inputs (Ext. OFF, Ext. Min, Ext. Max, heating/cooling, manual override (uncoupled from building automation), operation lock (key lock and remote operation configuration protection))
- 2 configurable signal relays for run signals and fault messages
- Slot for Wilo-CIF modules with interfaces for building automation BA (optional accessories: CIF modules Modbus RTU, Modbus TCP, BACnet MS/TP, BACnet IP, LON, PLR, CANopen)
- Wilo Net as a Wilo system bus for communication between Wilo products, e.g. Multi-Flow Adaptation; dual-pump operation and Wilo-Smart Gateway
- Automatic emergency operation with configurable pump speed for exceptional conditions, e.g. if bus communication fails or sensor values are unavailable
- Graphic colour display (4.3 inches) with one button manual operation level
- Use the Wilo-Assistant app to read and set operating data and – among other things – set up a commissioning protocol through the Bluetooth interface (no further accessories required)
- Integrated dual-pump management (twin-head pumps are prewired) when using 2 single pumps as a dual-pump unit, connection via Wilo Net
- Cable break detection when using an analogue signal (in connection with 2 – 10 V or 4 – 20 mA)
- Outdoor installation with weather protection possible in accordance with the installation and operating instructions
- Pre-set date and time
- Thermal insulation shell for heating applications
Scope of delivery
- Pump
- Optimised Wilo-Connector the same for all sizes
- 2x threaded cable gland M16 x 1.5
- Installation and operating instructions
Optional accessories:
- ClimaForm cold insulation to avoid the formation of condensate
- CIF module: Modbus TCP, Modbus RTU, BACnet IP, BACnet MS/TP, LON, PLR, CANopen
- Pt1000 (B) pipe surface contact sensor (for domestic hot water)
- Pt1000 (AA) sensor for installation in immersion sleeve
- Differential pressure sensor
- Wilo fluid temperature sensor (can be retrofitted for recording and displaying the fluid temperature, heat and cooling quantity measurement, and using the temperature-controlled control modes T-const., dT-const.)
| Operating data | |
|---|---|
| Min. fluid temperature Tmin | -10 °C |
| Max. fluid temperature Tmax | 90 °C |
| Min. ambient temperature Tmin | -10 °C |
| Max. ambient temperature Tmax | 40 °C |
| Maximum operating pressure PN | 10 bar |
| Minimum suction head at 50 °C m | 5 m |
| Minimum suction head at 95 °C m | 12 m |
| Minimum suction head at 110 °C | 18 m |
| Motor data | |
|---|---|
| Energy efficiency index (EEI) * | ≤ 0.17 |
| Mains connection | 1~230 V ±10%, 50/60 Hz |
| Min current Imin | 0.2 A |
| Max current Imax | 2.23 A |
| Rated power P2 | 433 W |
| Min. speed nmin | 650 1/min |
| Max. speed nmax | 4950 1/min |
| Power consumption P1 min | 10 W |
| Power consumption P1 max | 510 W |
| Emitted interference | EN 61800-3;2004+A1;2012 /residential area (C1) |
| Interference resistance | EN 61800-3;2004+A1;2012 /industrial environment (C2) |
| Insulation class | F |
| Protection class | IPX4D |
| Threaded cable connection | 5 x M16x1.5 |
| Materials | |
|---|---|
| Pump housing | Grey cast iron |
| Impeller | PPS-GF40 |
| Shaft | 1.4028, DLC-coated |
| Bearing | Carbon-graphite |
| Installation dimensions | |
|---|---|
| Pump connection | DN 32 |
| Port-to-port length L0 | 220 mm |
| Ordering information | |
|---|---|
| Brand | Wilo |
| Product description | Stratos MAXO 32/0,5-16 PN6/10-R7-OEM |
| Net weight, approx. m | 15.4 kg |
| Article number | 2222146 |