DL-E 50/160-5,5/2-S1

Article number: 2171064
Technical data
Hydraulic data
Minimum efficiency index (MEI) ≥0.4
Maximum operating pressure PN 16 bar
Note on dimensioning 16 bar to 120 °C, 13 bar to 140 °C
Min. fluid temperature Tmin -20 °C
Max. fluid temperature Tmax 140 °C
Min. ambient temperature Tmin 0 °C
Max. ambient temperature Tmax 40 °C
Drive
Mains connection 3~380 V, 50/60 Hz
Motor efficiency class IE4
Power consumption P1 max 6300 W
Rated power P2 5.5 kW
Max current Imax 10.6 A
Emitted interference EN 61800-3
Interference resistance EN 61800-3
Insulation class F
Protection class motor IP55
Motor protection PTC integrated
Materials
Pump housing Grey cast iron
Impeller Grey cast iron
Shaft Stainless steel
Shaft seal Q1Q1X4GG
Lantern 5.1301/EN-GJL-250 KTL-coated
Approved liquids (other liquids upon request)
Heating water (as per VDI 2035) yes
Heat carrier oil Special version at additional charge
Cooling and cold water circulation systems yes
Water-glycol mixtures (at 20 – 40 vol. % glycol and fluid temperature ≤ 40 °C) yes
Installation dimensions
Port-to-port length L0 340 mm
Pipe connection on the suction side DNs DN 50
Pipe connection on the discharge side DNd DN 50

CronoTwin-DL-E 50/160-5,5/2

L1, L2, L3: Mains connection: 3~440 V ±10%, 50/60 Hz; 3~400 V ±10%, 50/60 Hz; 3~380 V -5%/+10%, 50/60 Hz
PE: Protective conductor connection
DDG: Connection for differential pressure sensor
In1 (1): Actual value input 0-10 V/0-20 mA; 2-10 V/4-20 mA
GND (2): Ground connection for In1 and In2
+ 24 V (3): DC voltage output for an external consumer/sensor. Max load 60 mA
In2: Setpoint input 0-10 V/0-20 mA; 2-10 V/4-20 mA
MP: Multi-pump, interface for dual pump management
Ext. off: Control input “Overriding Off”The pump can be switched on or off via an external, potential-free contact (24 V DC/10 mA).
SBM:* Potential-free collective run signal (changeover contact according to VDI 3814)
SSM:* Potential-free collective fault signal (changeover contact according to VDI 3814)
aux: External pump cycling (only with dual pump operation). Pump cycling can be performed using an external, potential-free contact (24 VDC/10 mA)
DIP switch: 1: Switchover between operation (O) and service mode (S)2: Activate/deactivate the menu for access disable
Optional: IF-Modules for connection to the building automation

* Load capacity of contacts for SBM and SSM:

min.: 12 V DC/10 mA

max.: 250 V AC/1 A

Product data
Brand Wilo
Product description DL-E 50/160-5,5/2-S1
Article number 2171064
EAN number 4048482808994
Colour Green
Minimum order quantity 1
Date of sales availability 2015-09-01
Packaging
Packaging type One-way pallet
Packaging property Transport packaging
Pieces per pallet 1
Number per layer 1
Dimension, weight
Length with packaging 1200 mm
Length L 907 mm
Height with packaging 617 mm
Height H 453 mm
Width with packaging 1200 mm
Width W 925 mm
Gross weight, approx. m 229 kg
Net weight, approx. m 193 kg
Documents

Installation and operating instructions

Wilo-CronoLine-IL-E (5,5-7,5 kW), Wilo-CronoTwin-DL-E (5,5-7,5 kW)

Article Number 2160196
Edition 2022-08
Number of pages 260
Language de, en, fr, nl
PDF (27 MB)