Search
Contact
E-mail
Catalogue creation
My favorites
Product comparison
SiFire-FIRST-32/250-246-15E | Wilo

SiFire-FIRST-32/250-246-15E

Article number: 4240710
Technical data
Hydraulic data
Maximum operating pressure PN 16 bar
Number of pumps 1
Min. fluid temperature Tmin 4 °C
Max. fluid temperature Tmax 25 °C
Min. ambient temperature Tmin 4 °C
Max. ambient temperature Tmax 40 °C
Motor data
Mains connection 3~400 V, 50 Hz
Rated power P2 15 kW
Rated current IN 27.1 A
Power factor cos φ100 0.87
Rated speed n 2940 1/min
Protection class switchgear IP54
Materials
Pump housing 5.1301/EN-GJL-250 KTL-coated
Impeller Bronze
Shaft Stainless steel
Gasket material EPDM
Pipework material Steel
Installation dimensions
Pipe connection on the suction side DNs DN 50
Pipe connection on the discharge side DNd DN 50

SiFIre FIRST E

Dimensions H 1169 mm
Dimensions H1 1087 mm
Dimensions H2 390 mm
Dimensions P 568 mm
Dimensions HS 500 mm
Dimensions LS 400 mm
Pipe connection on the discharge side DNd DN 50
Pipe connection on the discharge side DNd PN 16
Pipe connection on the suction side DNs DN 50
Pipe connection on the suction side DNs PN 16
Dimensions L 1748 mm
Dimensions T 204 mm
Dimensions TS 200 mm
Dimensions HB 1472 mm
Dimensions w1 284 mm
Dimensions w2 284 mm
Product data
Brand Wilo
Product description SiFire-FIRST-32/250-246-15E
Article number 4240710
EAN number 4062679048147
Colour Red/black/silver
Minimum order quantity 1
Date of sales availability 2020-09-01
Packaging
Packaging type One-way pallet
Packaging property Sales packaging
Pieces per pallet 1
Number per layer 1
Dimension, weight
Length with packaging 768 mm
Length L 568 mm
Height with packaging 1602 mm
Height H 1472 mm
Width with packaging 1948 mm
Width W 1748 mm
Gross weight, approx. m 442 kg
Net weight, approx. m 402 kg
Tender text

Pressure-boosting system as a fully automatic compact unit for firefighting purposes in accordance with EN 12845.

Consisting of a pump with horizontal base frame - EN 733 - with spacer coupling, electric motor and one switch cabinet, fixed to a robust support structure.

Model E for the electric motor, equipped with firefighting dedicated controller, solid construction made of special profiled parts with cut-outs for forklift trucks and hooks to ensure trouble-free, safe transportation.

A circuit with dual pressure switch, pressure gauge, non-return valve, valve (secured from use by unauthorized personnel) for the main pump for automatic start. Equipped with a diaphragm installed directly on the main pump housing as standard, to prevent overheating in the event of zero flow.

Control E switchgear for fire extinguishing systems according to EN 12845.

Switchgear integrated in a sheet metal enclosure in accordance with protection class IP54. Very high control quality and very simple operation due to the firefighting dedicated controller, with multi-languages screen, easy navigation with simple menu and push button plus immediate operation status with symbols. Communication-ready controller for supervising systems operations.

The system has been mounted on the base frame with wires and pipes are ready for connection.

Inlet pressure:

The maximum inlet pressure must be taken into account when designing the system configuration (see Technical data). The maximum permissible inlet pressure is calculated from the maximum operating pressure of the system minus the maximum delivery head of the pump at Q = 0. For sprinkler systems in accordance with EN 12845, the water pressure should not exceed 12 bar. In sprinkler systems with a pronounced slope, in which the difference in height between the highest and lowest sprinkler is more than 45 m, the water pressure can be higher than 12 bar at the pump outlet or in the piping, provided that all of the system components are designed for this pressure level.

Installation of the pressure boosting pump under suction conditions.

For the main pump, it is necessary to install a supply tank with connection to the discharge pipe above the pump.

Volume flow

Up to 320 m³/h (89 l/s) system configuration for the main pump.

Switchgear/control device for fire water supply systems

Wilo-Control E (main pump with electric motor)

Hardware:

Fully electronic central control unit and electro-mechanical components, built in painted steel case, with protection class IP 54, control and display devices on the front door.

Features and functions:

The controller design is suitable for the performance of each motor-pump combination. The device comprises the following components:

Main switch: For switching the switchgear On/Off. (Unauthorized action in case of fire).

Display: Back lighted graphic LCD display, built into the switch cabinet door for operating and display purposes. Displays the operating data and the receptive current operating statuses of pump and the controller. The menu selection as well as the parameter input are done by push buttons on the front door.

Microprocessor: Integrated PLC logic with thresholds, counters, alarms, status; 24 VAC auxiliary power supply; advanced I/O wired functions. The respective programming configuration is strictly dependent on system and sprinkler installation.

Indicators: Long-life indicator lights to show, power supply status, pump running, motor status, pressure switch on, automatic mode excluded, manual reset, alarm stop.

Buttons: Push button to manage manual start or manual stop, alarm reset and menu selection.

Fuse protection: Protection fuses, capable of carrying the start current for a period of no less than 20s.

Motor startup: Contactor for direct-on-line starting up to 55kW.

Motor protection: Only for signaling.

Priming tank monitoring: By float switch to keep the water level at minimum 2/3 of the priming tank.

Power monitoring: Current, voltage, phases, cos phi and power of the pump.

Monitoring and controlling: Pump room temperature, working hours of the motor, pump status, pump statistics and starts, maintenance program.

Fault message and acknowledgment: All alarm messages are displayed via LEDs or the graphic LCD. The LEDs color and alarm code must be acknowledged.

Software:

  • Factory-programmed for fully automatic operation
  • Information regarding voltage, electric current and power of the pump

Menu navigation with text on display

Conforms to the following standards:

  • Fixed automatic sprinkler systems (EN 12845), part for pumps with electric motor
  • Electrical equipment of machines (EN 60204-1)
  • Low-voltage switchgear and control gear assemblies (EN 61439-1 and EN 61439-2)
  • Electromagnetic compatibility (EMC) — Immunity for industrial environments (EN 61000-6-2)
  • Electromagnetic compatibility (EMC) — Emission standard for residential, commercial and light-industrial environments (EN 61000-6-3)

Function description:

Wilo E control devices can be used to control pumps with an electric motor, sensors for pump management and the level of information. The microprocessor-controlled switchgear is used to control and regulate all required functions of a pressure-boosting system according to EN 12845, for test purposes or actual sprinkler events.

The operating logic for the fire extinguishing system is based on the cascade calibration of the pressure switches for starting the pump.

If a large amount of water is requested due to the opening of one or more circuits or due to a defective sprinkler, the pressure in the system decreases. As a result, the main pump is started using switchgear. If the electric main pump does not start in systems with multiple pumps (for example due to problems with the power supply), a pressure drop will activate the pressure switch of the standby pump, which starts this pump. In some cases, two or more electric pumps can be used.

As soon as the sprinkler circuit or gate valve, via which the sprinkler heads are supplied, is closed, pressure is built up in the system. The stop buttons on the front door must then be pressed to stop the pump.

Operating Data
Max. delivery head Hmax 76.0 m
Number of pumps 1
Fluid temperature T 4 °C
Ambient temperature T 4 °C
Maximum operating pressure PN 16 bar
Motor data
Mains connection 3~400 V, 50 Hz
Rated power P2 15 kW
Rated current IN 27.1 A
Power factor cos φ100 0.87
Rated speed n 2940 1/min
Protection class switchgear IP54
Materials
Pump housing 5.1301/EN-GJL-250 KTL-coated
Impeller Bronze
Shaft Stainless steel
Gasket material EPDM
Pipework material Steel
Installation dimensions
Pipe connection on the suction side DNs DN 50
Pipe connection on the discharge side DNd DN 50
Ordering information
Brand Wilo
Product description SiFire-FIRST-32/250-246-15E
Net weight, approx. m 402 kg
Article number 4240710
Documents

Group Statement

Group Statement REACH

Edition 2021-05
Number of pages 5
Language language neutral
PDF (327 KB)
Accessory

Break tank (1)

Fittings (8)

Noise control (6)

Pipe installation (8)

Valves/accessories (1)

Alarm signal (1)

Operating/service units (1)

Maintenance/replacement (15)

Services

With Wilo as your partner, you can not only be sure of choosing high-quality product solutions, but also of benefiting from a comprehensive, worry-free package of well thought-out services. We collaborate to develop a service concept tailored to your individual needs; with our expertise and personal consultancy, we make sure that the operation of your systems is as energy-efficient, reliable and economical as possible. All the while our competent Wilo service technicians are ready to assist you with fast, reliable and on-time support.

Read more

Recommended services

Maintenance
Maintenance COMFORT SiFire E
    
2219502

In order to ensure and guarantee operational reliability of the pumps/systems, it is recommended to have regular and DIN-compliant inspections and maintenance carried out by the works' own WILO SE Customer Service Department. The tasks are carried out in accordance with DIN 31051 / DIN EN 13306. The tasks comprise the following points:

  • Visual inspection of the pumps/systems
  • Mechanical check
  • Electrical check
  • Testing and possible filling of pressure vessels that may be on hand
  • Review and, if necessary, adjustment of the system parameters
  • Creating a maintenance protocol
  • Consumable materials are included in the contract price
  • Elimination of payroll and travel expenses for deployments between maintenance intervals (during normal service hours)

Scheduling and organisation is performed by WILO. Other individual maintenance offers are possible on request.

Maintenance PREMIUM SiFire E
    
2219555

In order to ensure and guarantee operational reliability of the pumps/systems, it is recommended to have regular and DIN-compliant inspections and maintenance carried out by the works' own WILO SE Customer Service Department. The tasks are carried out in accordance with DIN 31051 / DIN EN 13306. The tasks comprise the following points:

  • Visual inspection of the pumps/systems
  • Mechanical check
  • Electrical check
  • Testing and possible filling of pressure vessels that may be on hand
  • Checking the system parameters
  • Creating a maintenance protocol
  • Consumable materials are included in the contract price
  • Elimination of payroll and travel expenses for deployments between maintenance intervals (during and outside normal service hours)
  • Software updates
  • Includes wearing parts

Scheduling and organisation is performed by WILO. Other individual maintenance offers are possible on request.

Commissioning
Commissioning SiFire E
    
2219400

For perfect functioning of the pump(s) / system(s), it is recommended to have the commissioning carried out by the works' own WILO SE Customer Service Department. Optimum setting and efficient operation of the system are ensured as a result. Commissioning is comprised of the following points:

  • Commissioning of system(s) according to checklist
  • Parameterisation and setting of switchgear
  • Testing and adaptation of initial compressing of pressure tanks (filling up to 80 litres incl.)
  • Functional check of fitted system(s)
  • Practice-oriented operation instruction
  • Wilo commissioning protocol

The price for commissioning only applies to system(s) which have been installed in accordance with the installation and operating instructions and state-of-the-art technology. No costs for any materials which may be required are included.

More suitable services

Service packages
Service Package L SiFire E
    
2219712

The Wilo service offers predefined service packages in three sizes to make it easier to combine individual services.

The Wilo-Service package L includes:

  • Installation check
  • Supervision
  • Commissioning
  • Maintenance
  • Energy Solutions
  • WiloCare Premium
  • Wilo-Live Assistant

Optional add-on services:

  • System Optimisation
  • Repairs
  • Extended Warranty
Service Package M SiFire E
    
2219683

The Wilo service offers predefined service packages in three sizes to make it easier to combine individual services.

The Wilo-Service package M includes:

  • Installation check
  • Supervision
  • Commissioning
  • Maintenance
  • WiloCare Comfort
  • Wilo-Live Assistant

Optional add-on services:

  • System Optimisation
  • Energy Solutions
  • Repairs
  • Extended Warranty
Service Package S SiFire E
    
2219654

The Wilo service offers predefined service packages in three sizes to make it easier to combine individual services.

The Wilo-Service package S includes:

  • Installation check
  • Commissioning
  • Maintenance
  • WiloCare Basic
  • Wilo-Live Assistant

Optional add-on services:

  • System Optimisation
  • Energy Solutions
  • Supervision
  • Repairs
  • Extended Warranty
Wilo-Live Assistant
Wilo-Live Assistant Service
    
2216415

The Wilo-Live Assistant is a technical advisor at your side during pump service. By using the Wilo-Live Assistant, our expert advisers can support you in the boiler or equipment room via video transmission – live and in real time. You use your smartphone to show the installation set-up, while the Wilo expert follows everything on their screen. They can see the components as well as other details and can thus determine where the fault or breakdown originates. We prevent downtime and ensure operational reliability of your pumps and systems!

The Wilo-Live Assistant includes:

  • Interactive live support via video chat
  • Direct contact with an expert
  • Just-in-time solution to ensure maximum operational reliability of your pumps and systems
Extended Warranty
Extended Warranty SiFire E
    
2219602

In combination of a new pump or system Wilo offers an extended warranty of up to five years in combination with commissioning and maintenance by the Wilo Service.

Extended warranty includes:

  • Full protection and predictable cost security
  • Regular maintenance work by the Wilo Service
Supervision
Supervision SiFire E
    
2219336

Wilo supports during the concept phase to ensure quality work and cost efficiency. Our competent and qualified Wilo Service will support you with recommendations and technical advice throughout the entire project.

Supervision includes:

  • Regular on-site visits ensure the quality of information and advice
  • Technical consultancy, also available on site
  • Status report with recommendations after the visit
  • Comprehensive support from a Wilo expert
Installation
Installation SiFire E
    
2219371

The Wilo service offers installation of our pumps or pumping systems. We offer an end-to-end process from gathering information on site to installing our product in the overall plant. An optimal installation set-up and the interaction of various individual factors lay the foundation for long-term operational safety.

Installation includes:

  • Professional inspection
  • Provision of components/materials from Wilo and third-party suppliers
  • Installation of pipelines and electronics
  • Test runs
System Optimisation
System Optimisation SiFire E
    
2219266

The Wilo Service offers proactive system optimisation by optimising settings and doing minor adjustments to ensure operational reliability. System Optimisation includes among others:

  • Overhaul of pumps/systems to restore full performance
  • Addition of new technologies or functions in older systems to save on capital expenditures (retrofitting)
Energy Solutions
Energy Solutions SiFire E
    
2219301

Wilo Service offers a proactive support to point out possible energy savings. Our service creates an overview of all installed assets to show how the energy consumption of pumps or systems can be reduced. We offer targeted consultancy and analysis, including the involvement of subsidies as well as comprehensive support around the changeover to high-efficiency technologies. Wilo-Energy solution includes:

  • Detailed assessment of the life cycle costs (LCC analysis)
  • Energy audit including information about energy saving potential
  • Proactive recommendation of replacement options
  • Improving the environmental performance of your system
  • Support in the changeover to Wilo high-efficiency pumps
Repair
Repair SiFire E
    
2219625

Wilo Service draws on their competence and experience while consulting on site to decide whether the pump can actually be repaired on site or has to be sent in for a factory repair. Wilo also provides spare parts or a replacement pump to restore the operational reliability of the system.

Repair includes:

  • Verification and elimination of error causes by experienced Wilo experts
  • Non-binding estimate for repairs
  • Electric-hydraulic test run to ensure correct data regarding functionality, quality and performance of the pump or system
  • Coating of various pump or system components for an optimised efficiency factor
  • Use of genuine spare parts only
  • Documentation of the repair in the service report