P130-WM
Technical data | |
---|---|
Mains connection | 1~230 V, 50 Hz |
Rated power P2 | 30 W |
Control | Without frequency converter |
Activation type | Direct On Line (DOL) |
Electromagnetic compatibility | EN 61000 |
Connection standard | EN 1254 |
Installation | Wall-mounted installation |
Operating Data | |
---|---|
Max. inlet pressure | 6 bar |
Dimensions | |
---|---|
Dimensions H1 | 445,0 mm |
Dimensions H2 | 420,0 mm |
Dimensions H3 | 130,0 mm |
Dimensions H4 | 265,0 mm |
Dimensions H5 | 310,0 mm |
Dimensions L | 270,0 mm |
Product data | |
---|---|
Brand | Wilo |
Product description | P130-WM |
Article number | 2819501 |
EAN number | 5013608000674 |
Colour | Green/silver/grey |
Minimum order quantity | 1 |
Date of sales availability | 2012-06-01 |
Packaging | |
---|---|
Packaging type | Box |
Packaging property | Outer packaging |
Pieces per pallet | 10 |
Number per layer | 1 |
Dimension, weight | |
---|---|
Length with packaging | 270 mm |
Length L | 270 mm |
Height with packaging | 595 mm |
Height H | 445 mm |
Width with packaging | 270 mm |
Width W | 270 mm |
Gross weight, approx. m | 7 kg |
Net weight, approx. m | 7 kg |
The Wilo Comfort single pump wall mount pressurisation units are designed for use on heating or chilled water systems up to and including 3.0 bar cold fill pressures.
The unit is fitted with an 4 litre stainless steel break tank c/w type AB air gap to BS13077:2008 and water regulations 1999, Wras approved equilibrium ball float valve to BS1212 c/w strainer and a low water float for pump protection.
Each pump has an integral non return valve and quick release couplings for ease of maintenance. The pressure transducer monitors the system pressure and feeds a 0-10v signal to the comfort controller.
The unit is to be installed on systems with a maximum expansion of 300 litres.
Comfort Controller is complete with the following features:
- User friendly interface that has a 2 line LCD backlight display
- Healthy / fail LED
- Password protection
- Pump trip and fail alarms
- System leak alarm
- Excessive starts alarm
- Alarm log
- Hours Run
- Connectivity: BACnet = RS485 interface, BACnet MS/TP protocol
2 wire BACnet
Volt Free Contacts are supplied with terminals for common, normally open and normally closed.
(5A, 230V)
Pump no.1 trip, Pump no. 1 run, High Pressure, Low Pressure, Excess starts, Low water and Boiler Interlock (NC only)
(10A, 230V)
To be selected from Power fail, Common alarm, Common pressure alarm
Standards Applied:
Low Voltage and Machinery Directive 2006/42/EC, EMC Directive EMC 2004/108/EC, BSEN809, BS7074-1 to 3, BS13077:2008 and water regulations 1999.
Technical data | |
---|---|
Mains connection | 1~230 V, 50 Hz |
Control | Without frequency converter |
Operating Data | |
---|---|
Max. inlet pressure | 6 bar |
Ordering information | |
---|---|
Width W | 270 mm |