Sinum single-pump unit M20 400V
Article number: 2198860
Technical data | |
---|---|
Installation | Horizontal |
Connectable | yes |
Digital control unit | yes |
Max. operating pressure PN | 10 bar |
Min. working pressure | 2 |
Max. working pressure | 5 |
Min. refill pressure | 4 bar |
Max. refill pressure | 6 bar |
Min. fluid temperature T | 3 °C |
Max. fluid temperature T | 70 °C |
Max. feed temperature in the system | 105 °C |
Min. ambient temperature | 3 °C |
Max. ambient temperature | 40 °C |
Maximum allowed limit of glycol in % | 50 % |
Min. boiler output | 1600 kW |
Max. boiler output | 8400 kW |
Installation dimensions | |
---|---|
Connection inlet | G 1¼ |
Connection outlet | G 1¼ |
Tank connection | G 1 |
Replenishment connection | Rp ½ |
Motor data | |
---|---|
Mains frequency f | 50 Hz |
Phases | 1 |
Rated voltage U | 400 V |
Voltage tolerance | ±10 % |
Rated current IN | 7.2 A |
Protection class | IP54 |
Sound-pressure level | 55 dB |
Wilo-Sinum Pump M20
Product data | |
---|---|
Brand | Wilo |
Product description | Sinum single-pump unit M20 400V |
Article number | 2198860 |
EAN number | 4048482837772 |
Colour | White |
Minimum order quantity | 1 |
Date of sales availability | 2018-07-01 |
Packaging | |
---|---|
Packaging type | Euro pallet |
Packaging property | Transport packaging |
Pieces per pallet | 1 |
Number per layer | 1 |
Dimension, weight | |
---|---|
Length with packaging | 750 mm |
Length L | 553 mm |
Height with packaging | 1092 mm |
Height H | 937 mm |
Width with packaging | 590 mm |
Width W | 227 mm |
Gross weight, approx. m | 45.5 kg |
Net weight, approx. m | 35.3 kg |
For pressurisation, deaeration and topping up in sealed heating installations (acc. to EN12828) and chilled water (cooling) installations.
Sinum pump units are used for storage of expansion water, deaeration and topping up your installation automatically as an integrated controlled unit carried out with state of the art micro-electronics. The Sinum balanced pressure expansion equipment is sized according to the total system volume and the boiler or chiller load. The Sinum vessel is 80% efficient irrespective of the static height of the system. It is the ideal solution for large installations or high installations where standard diaphragm expansion equipment is limited.
Special features/product advantages
- Easy installation thanks to intuitive menu navigation in the HMI, large display and self-learning microprocessor.
- Different operating modes guarantee continuous degassing.
- Advanced technology ensures low power consumption, long service life and easy maintenance.
- Improved convenience through volumetric controls and automatic topping-up during the heating and cooling cycles.
- Modular design offers a high level of installation flexibility.
- Optional: Integration in existing building management systems through digital and analogue outputs.
Technical data | |
---|---|
Installation | Horizontal |
Connectable | yes |
Digital control unit | yes |
Max. operating pressure PN | 10 bar |
Max. working pressure | 5 |
Min. working pressure | 2 |
Min. refill pressure | 4 bar |
Max. refill pressure | 6 bar |
Min. fluid temperature T | 3 °C |
Max. fluid temperature T | 70 °C |
Min. ambient temperature | 3 °C |
Max. ambient temperature | 40 °C |
Max. feed temperature in the system | 105 °C |
Maximum allowed limit of glycol in % | 50 % |
Min. boiler output | 1600 kW |
Max. boiler output | 8400 kW |
Connection | |
---|---|
Inlet connection | G 1¼ |
Outlet connection | G 1¼ |
Tank connection | G 1 |
Replenishment connection | Rp ½ |
Motor data | |
---|---|
Mains frequency f | 50 Hz |
Phases | 1 |
Rated voltage U | 400 V |
Voltage tolerance | ±10 % |
Rated current IN | 7.2 A |
Protection class | IP54 |
Sound-pressure level | 55 dB |
Ordering information | |
---|---|
EAN number | 4048482837772 |
Item no. | 2198860 |
Make | Wilo |
Net weight, approx. | 35.3 kg |