P260
Datos técnicos | |
---|---|
Alimentación eléctrica | 1~230 V, 50 Hz |
Potencia nominal P2 P2 | 500 W |
Control | sin convertidor de frecuencia |
Tipo de arranque | Directo online (DOL) |
Compatibilidad electromagnética | EN 61000 |
Norma de conexión | EN 1254 |
Instalación | Instalación en el suelo |
Datos de funcionamiento | |
---|---|
Presión de entrada máx. | 8 bar |
Dimensiones | |
---|---|
Dimensiones H1 | 775,0 mm |
Dimensiones H2 | 730,0 mm |
Dimensiones H3 | 225,0 mm |
Dimensions H4 | 545,0 mm |
Dimensions H5 | 590,0 mm |
Dimensiones L | 455,0 mm |
Pressurisation Unit Wiring Diagram
Datos del producto | |
---|---|
Marca | Wilo |
Denominación del producto | P260 |
Referencia | 2819496 |
Número EAN | 5013608000629 |
Color | verde/plata/gris |
Cantidad mínima de pedido | 1 |
Disponibilidad en el mercado | 2012-06-01 |
Embalaje | |
---|---|
Tipo de embalaje | Europalé |
Propiedades del embalaje | Embalaje de transporte |
Número por palé | 4 |
Número por capa | 4 |
Medidas y pesos | |
---|---|
Longitud con embalaje | 1000 mm |
Longitud L | 455 mm |
Altura con embalaje | 925 mm |
Altura H | 775 mm |
Ancho con embalaje | 800 mm |
Ancho W | 350 mm |
Peso bruto aproximado m | 50 kg |
Peso neto aproximado m | 35 kg |
The Wilo Comfort twin pump pressurisation units (duty / standby) are designed for use on heating or chilled water systems up to and including 3.5, 6.0 and 8.0 bar cold fill pressures.
The unit is fitted with an 18 litre polypropylene break tank c/w type AB air gap to BS13077:2008 and water regulations 1999, Wras approved equilibrium ball float valve to BS1212 and a low water float switch and strainers for pump protection.
Each pump is fitted with a non return valve and quick release couplings for ease of maintenance. The pressure transducer monitors the system pressure and feeds a 0-10v signal to the comfort controller.
Comfort Controller is complete with the following features:
- User friendly interface that has a 2 line LCD backlight display
- Healthy / fail LED
- Password protection
- System Fill for initial fill of system
- Pump check routine, that runs both pumps for 2 seconds if inactive for 7-90 days
- Pump trip and fail alarms
- System leak alarm
- Excessive starts alarm
- Alarm log
- Hours Run
- Automatic duty rotation
- Connectivity: BACnet = RS485 interface, BACnet MS/TP protocol
2 wire BACnet
Volt Free Contacts are supplied with terminals for common, normally open and normally closed.
(5A, 230V)
Pump no.1 trip, Pump no. 1 run, Pump no.2 trip, Pump no. 2 run, High Pressure, Low Pressure, Excess starts, Low water and Boiler Interlock (NC only)
(10A, 230V)
To be selected from Power fail, Common alarm, Common pressure alarm
Standards Applied:
Low Voltage and Machinery Directive 2006/42/EC, EMC Directive EMC 2004/108/EC, BSEN809, BS7074-1 to 3, BS13077:2008 and water regulations 1999.
Datos técnicos | |
---|---|
Alimentación eléctrica | 1~230 V, 50 Hz |
Control | sin convertidor de frecuencia |
Datos de funcionamiento | |
---|---|
Presión de entrada máx. | 8 bar |
Información de pedidos | |
---|---|
Ancho W | 350 mm |