P135-TS
Datos técnicos | |
---|---|
Alimentación eléctrica | 1~230 V, 50 Hz |
Potencia nominal P2 P2 | 370 W |
Control | sin convertidor de frecuencia |
Tipo de arranque | Directo online (DOL) |
Compatibilidad electromagnética | EN 61000 |
Norma de conexión | EN 1254 |
Instalación | Instalación en el suelo |
Datos de funcionamiento | |
---|---|
Presión de entrada máx. | 8 bar |
Dimensiones | |
---|---|
Dimensiones H1 | 775,0 mm |
Dimensiones H2 | 730,0 mm |
Dimensiones H3 | 225,0 mm |
Dimensions H4 | 545,0 mm |
Dimensions H5 | 590,0 mm |
Dimensiones L | 455,0 mm |
Datos del producto | |
---|---|
Marca | Wilo |
Denominación del producto | P135-TS |
Referencia | 2819498 |
Número EAN | 5013608000643 |
Color | verde/plata/gris |
Cantidad mínima de pedido | 1 |
Disponibilidad en el mercado | 2012-06-01 |
Embalaje | |
---|---|
Tipo de embalaje | Europalé |
Propiedades del embalaje | Embalaje de transporte |
Número por palé | 4 |
Número por capa | 4 |
Medidas y pesos | |
---|---|
Longitud con embalaje | 1000 mm |
Longitud L | 455 mm |
Altura con embalaje | 925 mm |
Altura H | 775 mm |
Ancho con embalaje | 800 mm |
Ancho W | 350 mm |
Peso bruto aproximado m | 50 kg |
Peso neto aproximado m | 35 kg |
The Wilo Comfort Twin System pressurisation units are designed for use on heating or chilled water systems and include 1 pump per system, each pump capable of up to and including 3.5, 6.0 and 8.0 bar cold fill pressures.
The unit is fitted with an 18 litre polypropylene break tank c/w type AB air gap to BS13077:2008 and water regulations 1999, Wras approved equilibrium ball float valve to BS1212 and a low water float switch and strainers for pump protection.
Each pump is fitted with a non return valve and quick release couplings for ease of maintenance. The two pressure transducers monitor each system pressure individually and feed 0-10v signals to the comfort controller.
Comfort Controller is complete with the following features:
- User friendly interface that has a 2 line LCD backlight display
- Healthy / fail LED
- Password protection
- System Fill for initial fill of system
- Pump check routine, that runs both pumps for 2 seconds if inactive for 7-90 days
- Pump trip and fail alarms
- System leak alarm
- Excessive starts alarm
- Alarm log
- Hours Run
- Connectivity: BACnet = RS485 interface, BACnet MS/TP protocol
2 wire BACnet
Volt Free Contacts are supplied with terminals for common, normally open and normally closed.
(5A, 230V)
Pump no.1 trip, Pump no. 1 run, High Pressure, Low Pressure, Excess starts, Low water and Boiler Interlock (NC only)
(10A, 230V)
To be selected from Power fail, Common alarm, Common pressure alarm
Standards Applied:
Low Voltage and Machinery Directive 2006/42/EC, EMC Directive EMC 2004/108/EC, BSEN809, BS7074-1 to 3, BS13077:2008 and water regulations 1999.
Datos técnicos | |
---|---|
Alimentación eléctrica | 1~230 V, 50 Hz |
Control | sin convertidor de frecuencia |
Datos de funcionamiento | |
---|---|
Presión de entrada máx. | 8 bar |
Información de pedidos | |
---|---|
Ancho W | 350 mm |