ElectronicControl
ElectronicControl
特点/产品优势
- Easy adjustment and operation
- Large display with simplified menu and navigation in addition to LED status indicator
- Meets the EMC standards for domestic use (EN 61000-6-2 and EN 61000-6-3)
- Comfort functions: PID (APP function), frost protection automatic system AIS, automatic restart after error ART
- Float switch can be connected optionally
结构型式
Water-cooled frequency converter with built-in pressure and flow monitor
应用
For controlling pumps in the fields:
- Water supply
- Rainwater utilisation
- Irrigation and spraying
设备/功能
- With 1.4 m connection cable and plug pre-cabled
- Pre-cabled motor cable with cable end sleeves
- Built-in EMC filter
- with built-in pressure and flow monitors
- Restoration of the selected settings after interruption of the power supply
型号代码
示例; | ElectronicControl MT6 |
ElectronicControl | 带变频器的控制器 |
M | ElectronicControl 1~230 V 电源 |
T | 电机电源 T = 3~230 V,M = 1~230 V |
6 | 最高电耗,单位 A |
技术数据
- Max. operating pressure: 15 bar
- Setting range: 0.5 to 12 bar
- Max. volume flow: 15 m3/h
- Max. fluid temperature: 40 °C
- Min. fluid temperature: 0 °C
- Max. ambient temperature: 50 °C
- Input voltage: 1~230 V, 50/60 Hz
- Excess current protection: +20 % of the maximum current consumption over a period of 10 s
- Protection class: IP55
材料
- Safety disk AISI 304 L
- Pressure sensor: Al2O3
- Cooling module: CuZn33
- Housing, safety disk and cover: Polyamide: 6 - 50% glass fibres
- Flow monitor: Acetal resin Hostaform C2521 14
- Seals: Natural rubber
- Cap for minimum flow rate: Noryl GFN2V
类型
- Complete and automatic protection against:
- Excess current
- Dry run
- Undervoltage and overvoltage
- Excess temperature
- Short-circuit
- History log: operating hours, number of starts, number of connection to the power supply, type and number of alarm signals since commissioning the device
出厂状态
1 control device Electronic Control incl.:
- Pre-cabling with 1.4 m connection cable and plug
- Pre-cabled motor cable with cable end sleeves
- Installation and operating instructions